Tracking Number>>Abated?>>Location Name>>Location Address>>IssueDate>>Statute Rule>>Statute Title>>Abated Date>>Infraction Location>>Infraction Description>>Location Address 2>>Location City>>Location State>>Location Zip Code>>Location Zip Code 2>
"FPVIO-25-1740756951">>"False">>"Adventure Land Academy">>"Adventure Land Academy">>"02/28/2025">>"906.1">>"Where required.">>"">>"2nd floor">>"Fire Extinguisher required">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740757049">>"False">>"Adventure Land Academy">>"Adventure Land Academy">>"02/28/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740685142">>"False">>"">>"">>"02/27/2025">>"315.3.1">>"Ceiling clearance.">>"">>"kitchen, above prep line ">>"Storage shall not be within 18 inches of ceiling in sprinklered building">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740685467">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/27/2025">>"704.2">>"Opening protectives.">>"">>"BOH Mall Security ">>"Fire doors shall not be blocked open or obstructed">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740759269">>"False">>"">>"">>"02/28/2025">>"1008.2">>"Illumination required.">>"">>"throughout 4 and 5
party room over tv">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1740769212">>"False">>"">>"">>"02/28/2025">>"607.3.3.2    ">>"Grease accumulation.   ">>"">>"">>"Kitchen hood cleaning required - Grease accumulation removed/RN">>"1st Floor">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740771097">>"False">>"Bluestone Lane">>"Bluestone Lane">>"02/28/2025">>"904.5.1">>"System test.">>"">>"kitchen">>"Wet chemical suppression system inspection required (6 months)/RN">>"E8A">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740760596">>"False">>"">>"">>"02/28/2025">>"906.9">>"Extinguisher installation.">>"">>"suite 207">>"Fire extinguisher shall be properly mounted/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1740760799">>"False">>"">>"">>"02/28/2025">>"1008.2">>"Illumination required.">>"">>"2 lights">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1740682974">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/27/2025">>"1031.1.1">>"Storage.">>"">>"Stair 1 JCP ">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740683091">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/27/2025">>"404.2.1">>"Fire evacuation plans.">>"">>"Sprinkler rooms throughout ">>"Provide sprinkler zone maps in each sprinkler room">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740681974">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/27/2025">>"1031.1.1">>"Storage.">>"">>"BOH Old Navy">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740682108">>"False">>"">>"">>"02/27/2025">>"1031.1.1">>"Storage.">>"">>"Mall corridor ">>"Storage not permitted in means of egress/RN">>"1041">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740683190">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/27/2025">>"704.2">>"Opening protectives.">>"">>"JCP North D">>"Fire doors shall not be blocked open or obstructed">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740683401">>"False">>"">>"">>"02/27/2025">>"1031.1.1">>"Storage.">>"">>"Mall corridor ">>"Storage not permitted in means of egress/RN">>"1063">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740685052">>"False">>"">>"">>"02/27/2025">>"1008.2">>"Illumination required.">>"">>"kitchen- above prep line">>"Emergency egress lighting shall be maintained">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740683241">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/27/2025">>"704.2">>"Opening protectives.">>"">>"JCP north D">>"Fire doors shall not be blocked open or obstructed">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740683324">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/27/2025">>"1031.1.1">>"Storage.">>"">>"BOH American Eagle ">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1741022752">>"False">>"">>"">>"03/03/2025">>"604.3">>"Working space and clearance.">>"">>"managers office- storage in front of electrical panels ">>"Storage not permitted within 36 inches of electrical service equipment">>"One Garden State Plaza">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741023466">>"False">>"">>"">>"03/03/2025">>"904.5.1">>"System test.">>"">>"cookline">>"Wet chemical suppression system inspection required (6 months)/RN">>"2225">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741022246">>"False">>"">>"">>"03/03/2025">>"1008.2">>"Illumination required.">>"">>"kitchen">>"Emergency egress lighting shall be maintained">>"A 8B">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741022713">>"False">>"">>"">>"03/03/2025">>"1008.2">>"Illumination required.">>"">>"emergency light above registers">>"Emergency egress lighting shall be maintained">>"One Garden State Plaza">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741023536">>"False">>"">>"">>"03/03/2025">>"607.3.3">>"Cleaning.">>"">>"kitchen exhaust system ">>"Kitchen exhaust system overdue for 6 month cleaning/RN">>"2225">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741026093">>"False">>"">>"">>"03/03/2025">>"607.3.3">>"Cleaning.">>"">>"kitchen- exhaust hoods">>"Kitchen exhaust system overdue for 6 month cleaning/RN">>"One Garden State Plaza">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741026130">>"False">>"">>"">>"03/03/2025">>"904.5.1">>"System test.">>"">>"kitchen suppression system">>"Wet chemical suppression system inspection required (6 months)/RN">>"One Garden State Plaza">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741024148">>"False">>"">>"">>"03/03/2025">>"904.5.1">>"System test.">>"">>"kitchen suppression system">>"Wet chemical suppression system inspection required (6 months)/RN">>"FC 10">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741024275">>"False">>"">>"">>"03/03/2025">>"906.2">>"General requirements.">>"">>"tenant space">>"Fire extinguisher overdue for maintenance/inspection/RN">>"FC 10">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741013644">>"False">>"">>"">>"03/03/2025">>"903.5">>"Testing and maintenance.">>"">>"Fire Sprinkler system">>"Automatic Sprinkler System - must be inspected and tested per NFPA 25 - reports must be submitted">>"">>"">>"">>"">>"">
"FPVIO-25-1741018578">>"False">>"">>"">>"03/03/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1740771793">>"False">>"">>"">>"02/28/2025">>"904.5.1">>"System test.">>"">>"kitchen- cookline ">>"Wet chemical suppression system inspection required (6 months)/RN">>"Space E-8B">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741013602">>"False">>"">>"">>"03/03/2025">>"610.1">>"General.">>"">>"Hallway ">>"Repair emergency light">>"">>"">>"">>"">>"">
"FPVIO-25-1741018592">>"False">>"">>"">>"03/03/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741022191">>"False">>"">>"">>"03/03/2025">>"904.5.1">>"System test.">>"">>"kitchen cookline">>"Wet chemical suppression system inspection required (6 months)/RN">>"A 8B">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741022214">>"False">>"">>"">>"03/03/2025">>"607.3.3">>"Cleaning.">>"">>"kitchen exhaust">>"Kitchen exhaust system overdue for 6 month cleaning/RN">>"A 8B">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741021156">>"False">>"">>"">>"03/03/2025">>"5303.5.3">>"Securing compressed gas containers, cylinders and tanks.">>"">>"kitchen, carbon dioxide tanks x6">>"Compressed gas cylinders/containers shall be secured">>"2230">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741021736">>"False">>"">>"">>"03/03/2025">>"901.4.1">>"Fire protection systems.">>"">>"walk in box">>"Fire protection system performance shall not be reduced, sprinkler packaging removed">>"B 3A">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740680930">>"False">>"">>"">>"02/27/2025">>"5:70-4.9(d)">>"Automatic fire and carbon monoxide alarms">>"">>"tenant space ">>"Carbon Monoxide Detectors shall be installed">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740596039">>"False">>"">>"">>"02/26/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740596789">>"False">>"">>"">>"02/26/2025">>"906.2">>"General requirements.">>"">>"">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740595828">>"False">>"">>"">>"02/26/2025">>"1013.1">>"Exit signs.">>"">>"">>"Exit/direction signs shall be maintained/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740596025">>"False">>"">>"">>"02/26/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740597219">>"False">>"">>"799 ROUTE 17">>"02/26/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740673731">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/27/2025">>"703.1">>"Maintaining protection.">>"">>"BOH Reebok">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740673806">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/27/2025">>"1031.1.1">>"Storage.">>"">>"BOH Perfuroma">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740672875">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/27/2025">>"1031.1.1">>"Storage.">>"">>"BOH Victoria's Secret">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740673016">>"False">>"">>"">>"02/27/2025">>"1031.1.1">>"Storage.">>"">>"Mall Corridor ">>"Storage not permitted in means of egress/RN">>"1018">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740426636">>"False">>"">>"">>"02/24/2025">>"102.1.1">>"">>"">>"Rear Exit">>"Conditions liable to interfere with egress of occupants or operation of fire department">>"">>"">>"">>"">>"">
"FPVIO-25-1740426678">>"False">>"">>"">>"02/24/2025">>"605.3.1">>"Labeling.">>"">>"Electrical Panel">>"Locate and label circuit breakers for emergency lighting">>"">>"">>"">>"">>"">
"FPVIO-25-1740426446">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"BOHh CPK">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740426513">>"False">>"">>"">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"Mall corridor ">>"Storage not permitted in means of egress/RN">>"2230">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740500191">>"False">>"">>"">>"02/25/2025">>"903.5">>"Testing and maintenance.">>"">>"Fire Sprinkler System ">>"Automatic Sprinkler System - must be inspected and tested per NFPA 25 - reports must be submitted">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740595335">>"False">>"">>"">>"02/26/2025">>"906.2">>"General requirements.">>"">>"">>"Fire extinguisher serviced or replaced">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740595662">>"False">>"">>"">>"02/26/2025">>"1008.2">>"Illumination required.">>"">>"">>"Emergency egress lighting shall be maintained">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740500229">>"False">>"">>"">>"02/25/2025">>"901.6">>"Inspection, testing and maintenance, any installed.">>"">>"">>"All Fire Protection systems must be maintained. Service Fire Alarm System and forward the report to this office.">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740594988">>"False">>"">>"">>"02/26/2025">>"1013.1">>"Exit signs.">>"">>"Loading dock exit">>"Exit/direction signs shall be maintained/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740680031">>"False">>"">>"">>"02/27/2025">>"906.2">>"General requirements.">>"">>"rear door">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740680105">>"False">>"">>"">>"02/27/2025">>"904.5.1">>"System test.">>"">>"tenant space">>"Wet chemical suppression system inspection required (6 months)/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740679787">>"False">>"">>"">>"02/27/2025">>"607.3.3">>"Cleaning.">>"">>"">>"Kitchen exhaust system overdue for 6 month cleaning/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740679826">>"False">>"">>"">>"02/27/2025">>"904.5.1">>"System test.">>"">>"">>"Wet chemical suppression system inspection required (6 months)/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740680134">>"False">>"">>"">>"02/27/2025">>"607.3.3.2    ">>"Grease accumulation.   ">>"">>"cookline">>"Grease accumulation of kitchen suppression nozzles shall be removed/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740680803">>"False">>"">>"">>"02/27/2025">>"604.5">>"Extension cords.">>"">>"kitchen, near ice maker">>"Extension cords shall not be utilized for permanent wiring">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740680832">>"False">>"">>"">>"02/27/2025">>"5303.5.3">>"Securing compressed gas containers, cylinders and tanks.">>"">>"kitchen, soda system">>"Compressed gas cylinders/containers shall be secured">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740680205">>"False">>"">>"">>"02/27/2025">>"607.3.3.2    ">>"Grease accumulation.   ">>"">>"deep fryer ">>"Grease accumulation on cooking appliances shall be removed/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740680247">>"False">>"">>"">>"02/27/2025">>"607.3.3.2    ">>"Grease accumulation.   ">>"">>"all kitchen exhaust hoods ">>"Kitchen hood cleaning required - Grease accumulation removed/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740674098">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/27/2025">>"704.2">>"Opening protectives.">>"">>"BOH Macy's">>"Fire doors shall not be blocked open or obstructed">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740674194">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/27/2025">>"1031.1.1">>"Storage.">>"">>"BOH Chick-Fil-a">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740673903">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/27/2025">>"703.1">>"Maintaining protection.">>"">>"BOH Perfuroma">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740674046">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/27/2025">>"1031.1.1">>"Storage.">>"">>"BOH Macy's">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740674348">>"False">>"">>"">>"02/27/2025">>"607.3.3">>"Cleaning.">>"">>"Hood System">>"Grease cleaning required ">>"">>"">>"">>"">>"">
"FPVIO-25-1740676780">>"False">>"">>"">>"02/27/2025">>"610.1">>"General.">>"">>"Front Door">>"Repair emergency light">>"">>"">>"">>"">>"">
"FPVIO-25-1740679477">>"False">>"">>"">>"02/27/2025">>"906.2">>"General requirements.">>"">>"">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740674495">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/27/2025">>"703.1">>"Maintaining protection.">>"">>"BOH Jerk Shack">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740674511">>"False">>"">>"">>"02/27/2025">>"901.6.3">>"Carbon monoxide alarms.">>"">>"Store">>"Carbon Monoxide (CO) alarm must be installed and maintained in accordance with NFPA 720 and manufacturer">>"">>"">>"">>"">>"">
"FPVIO-25-1741026170">>"False">>"">>"">>"03/03/2025">>"906.2">>"General requirements.">>"">>"tenant space">>"Fire extinguisher overdue for maintenance/inspection/RN">>"One Garden State Plaza">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741282398">>"False">>"">>"">>"03/06/2025">>"604.5">>"Extension cords.">>"">>"Throughout ">>"Extension cords shall not be utilized for permanent wiring">>"">>"">>"">>"">>"">
"FPVIO-25-1741282485">>"False">>"">>"">>"03/06/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741281882">>"False">>"">>"">>"03/06/2025">>"906.2">>"General requirements.">>"">>"throughout ">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741282243">>"False">>"">>"">>"03/06/2025">>"1013.1">>"Exit signs.">>"">>"">>"Exit/direction signs shall be maintained/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741282609">>"False">>"Borough of Paramus Ted D'Uva Community Center">>"Borough of Paramus Ted D'Uva Community Center">>"03/06/2025">>"1013">>"EXIT SIGNS">>"">>"Lobby">>"Repair Exit Sign (Battery Operation)">>"">>"Paramus">>"">>"">>"">
"FPVIO-25-1741283340">>"False">>"">>"">>"03/06/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741284656">>"False">>"">>"">>"03/06/2025">>"1031.3">>"Obstructions.">>"">>"">>"Means of egress shall not be obstructed">>"">>"">>"">>"">>"">
"FPVIO-25-1741283290">>"False">>"">>"">>"03/06/2025">>"906.2">>"General requirements.">>"">>"throughout ">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741283313">>"False">>"">>"">>"03/06/2025">>"1013.1">>"Exit signs.">>"">>"">>"Exit/direction signs shall be maintained/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741202839">>"False">>"">>"">>"03/05/2025">>"906.2">>"General requirements.">>"">>"throughout ">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741202950">>"False">>"">>"">>"03/05/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741202764">>"False">>"">>"">>"03/05/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741202811">>"False">>"">>"">>"03/05/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741203026">>"False">>"">>"">>"03/05/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741277644">>"False">>"">>"">>"03/06/2025">>"607.3.3">>"Cleaning.">>"">>"Kitchen Hood">>"Grease Cleaning overdue for service">>"">>"">>"">>"">>"">
"FPVIO-25-1741281644">>"False">>"">>"">>"03/06/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741270204">>"False">>"">>"">>"03/06/2025">>"610.1">>"General.">>"">>"Viloations Back Office">>"Repair Emergency Light">>"">>"">>"">>"">>"">
"FPVIO-25-1741273653">>"False">>"Borough of Paramus Life Safety Building">>"Borough of Paramus Life Safety Building">>"03/06/2025">>"1013">>"EXIT SIGNS">>"">>"2nd floor north stairwell">>"Repair Exit Sign (Battery Operation) #2">>"">>"Paramus">>"">>"">>"">
"FPVIO-25-1741700451">>"False">>"My Sneaker Palace">>"My Sneaker Palace">>"03/11/2025">>"315.3.1">>"Ceiling clearance.">>"">>"rear area">>"Storage shall not be within 18 inches of ceiling in sprinklered building">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1741700485">>"False">>"My Sneaker Palace">>"My Sneaker Palace">>"03/11/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1741633507">>"False">>"">>"">>"03/10/2025">>"906.2">>"General requirements.">>"">>"Throughout ">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741700426">>"False">>"My Sneaker Palace">>"My Sneaker Palace">>"03/11/2025">>"906.2">>"General requirements.">>"">>"">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1741705625">>"False">>"">>"">>"03/11/2025">>"1013">>"EXIT SIGNS">>"">>"Rear Exit">>"Repair Exit Light (Battery Operation)">>"">>"">>"">>"">>"">
"FPVIO-25-1741710152">>"False">>"">>"">>"03/11/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741713395">>"False">>"">>"">>"03/11/2025">>"1008.2">>"Illumination required.">>"">>"sales floor ">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1741706833">>"False">>"">>"">>"03/11/2025">>"605.6">>"Unapproved conditions.">>"">>"Basement Electrical Panels">>"Cover open panels on the electrical panel ">>"">>"">>"">>"">>"">
"FPVIO-25-1741710039">>"False">>"">>"">>"03/11/2025">>"906.2">>"General requirements.">>"">>"throughout ">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741285401">>"False">>"">>"">>"03/06/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741286731">>"False">>"">>"">>"03/06/2025">>"901.6.3">>"Carbon monoxide alarms.">>"">>"EMS 2">>"Carbon Monoxide (CO) alarm must be maintained in accordance with NFPA 720 and manufacturer">>"">>"">>"">>"">>"">
"FPVIO-25-1741285245">>"False">>"">>"">>"03/06/2025">>"703.1">>"Maintaining protection.">>"">>"screening room">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741285347">>"False">>"">>"">>"03/06/2025">>"604.5">>"Extension cords.">>"">>"conference room">>"Extension cords shall not be utilized for permanent wiring">>"">>"">>"">>"">>"">
"FPVIO-25-1741288249">>"False">>"">>"">>"03/06/2025">>"1013">>"EXIT SIGNS">>"">>"Rear Exit">>"Repair Exit Lights (Battery Operation)">>"">>"">>"">>"">>"">
"FPVIO-25-1741360712">>"False">>"">>"">>"03/07/2025">>"610.1">>"General.">>"">>"Hallway">>"Repair Emergency Light">>"">>"">>"">>"">>"">
"FPVIO-25-1741360976">>"False">>"">>"">>"03/07/2025">>"610.1">>"General.">>"">>"Office">>"Repair Emergency Light (2)">>"">>"">>"">>"">>"">
"FPVIO-25-1741359934">>"False">>"">>"">>"03/07/2025">>"1013">>"EXIT SIGNS">>"">>"Rear stairwell">>"Repair Exit Light (Battery Operation)">>"">>"">>"">>"">>"">
"FPVIO-25-1741359995">>"False">>"">>"">>"03/07/2025">>"1013">>"EXIT SIGNS">>"">>"Stairwell">>"Repair Exit Light (Battery Operation)">>"">>"">>"">>"">>"">
"FPVIO-25-1741199753">>"False">>"">>"">>"03/05/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-00108">>"False">>"Forest Office Center">>"210 E. Route 4">>"03/04/2025">>"1203.4.3">>"Records.">>"">>"">>"Annual Emergency Generator inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1741100549">>"False">>"">>"">>"03/04/2025">>"3205.6">>"Designation of storage heights.">>"">>"Aisle 45">>"Lower Storage Height">>"">>"">>"">>"">>"">
"FPVIO-25-00106">>"False">>"Forest Office Center">>"210 E. Route 4">>"03/04/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-00107">>"False">>"Forest Office Center">>"210 E. Route 4">>"03/04/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1741100739">>"False">>"">>"">>"03/04/2025">>"3205.6">>"Designation of storage heights">>"">>"Aisle 33">>"Lower Storage Height">>"">>"">>"">>"">>"">
"FPVIO-25-1741112274">>"False">>"">>"">>"03/04/2025">>"1013.1">>"Exit signs.">>"">>"kitchen entrance door-exit/emergency sign">>"Exit/direction signs shall be maintained/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741112502">>"False">>"">>"">>"03/04/2025">>"901.6.3">>"Records.">>"">>"structure">>"Annual Fire Sprinkler shall be conducted and inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741100786">>"False">>"">>"">>"03/04/2025">>"3205.6">>"Designation of storage heights">>"">>"Aisle 23">>"Lower Storage Height">>"">>"">>"">>"">>"">
"FPVIO-25-1741100850">>"False">>"">>"">>"03/04/2025">>"3205.6">>"Designation of storage heights">>"">>"Aisle 35">>"Lower Storage Height">>"">>"">>"">>"">>"">
"FPVIO-25-1741031050">>"False">>"">>"">>"03/03/2025">>"604.5">>"Extension cords.">>"">>"stock room near electrical panel">>"Extension cords shall not be utilized for permanent wiring">>"">>"">>"">>"">>"">
"FPVIO-25-1741031236">>"False">>"">>"">>"03/03/2025">>"906.2">>"General requirements.">>"">>"throughout">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741030682">>"False">>"">>"">>"03/03/2025">>"906.2">>"General requirements.">>"">>"throughout ">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741030766">>"False">>"">>"">>"03/03/2025">>"509.2">>"Equipment access.">>"">>"">>"Access to utilities and/or building controls shall not be obstructed (electrical panel)">>"">>"">>"">>"">>"">
"FPVIO-25-1741031254">>"False">>"">>"">>"03/03/2025">>"509.2">>"Equipment access.">>"">>"electrical panel">>"Access to utilities and/or building controls shall not be obstructed/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741031985">>"False">>"">>"">>"03/03/2025">>"509.1">>"Identification.">>"">>"tenant space">>"rear door to tenant space shall be labeled/identifiable. ">>"FC 11">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-00105">>"False">>"Raymour & Flanigan Outlet">>"250 E. Route 4">>"03/04/2025">>"901.4.1">>"Fire protection systems.">>"">>"Sprinkler report shows 4 deficiencies that must be repaired.">>"Fire Protection system maintenance required/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1741031732">>"False">>"">>"">>"03/03/2025">>"906.2">>"General requirements.">>"">>"tenant space">>"Fire extinguisher overdue for maintenance/inspection/RN">>"FC 9">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741031773">>"False">>"">>"">>"03/03/2025">>"904.5.1">>"System test.">>"">>"cookline">>"Wet chemical suppression system inspection required (6 months)/RN">>"FC 9">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741197492">>"False">>"">>"">>"03/05/2025">>"1013.1">>"Exit signs.">>"">>"Upstairs training area">>"Exit/direction signs shall be maintained/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741197622">>"False">>"">>"">>"03/05/2025">>"1013.1">>"Exit signs.">>"">>"Loewer training area">>"Exit/direction signs shall be maintained/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741196473">>"False">>"">>"">>"03/05/2025">>"906.2">>"General requirements.">>"">>"Throughout ">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741197442">>"False">>"">>"">>"03/05/2025">>"1013.1">>"Exit signs.">>"">>"Front entrance">>"Exit/direction signs shall be maintained/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741197893">>"False">>"">>"">>"03/05/2025">>"1013.1">>"Exit signs.">>"">>"mid level storage">>"Exit/direction signs shall be maintained/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741199634">>"False">>"">>"">>"03/05/2025">>"1008.2">>"Illumination required.">>"">>"throughout GX area">>"Emergency egress lighting shall be maintained">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741199738">>"False">>"">>"">>"03/05/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741198938">>"False">>"">>"">>"03/05/2025">>"1013.1">>"Exit signs.">>"">>"both exit signs pool area ">>"Exit/direction signs shall be maintained/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741199285">>"False">>"">>"">>"03/05/2025">>"1008.2">>"Illumination required.">>"">>"emergency lights for right side racquetball court">>"Emergency egress lighting shall be maintained">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741113826">>"False">>"">>"">>"03/04/2025">>"1008.2">>"Illumination required.">>"">>"">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1741186989">>"False">>"">>"">>"03/05/2025">>"102.1.1">>"">>"">>"Hallway to waiting Room">>"Permanently remove obstructions away from the exit door ">>"">>"">>"">>"">>"">
"FPVIO-25-1741112837">>"False">>"">>"">>"03/04/2025">>"901.6.3">>"Records.">>"">>"structure">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741113602">>"False">>"">>"">>"03/04/2025">>"1008.2">>"Illumination required.">>"">>"">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1741189484">>"False">>"">>"">>"03/05/2025">>"906.2">>"General requirements.">>"">>"Office">>"Fire extinguishers must be properly serviced and tagged">>"">>"">>"">>"">>"">
"FPVIO-25-1741195929">>"False">>"">>"">>"03/05/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741195999">>"False">>"">>"">>"03/05/2025">>"1013.1">>"Exit signs.">>"">>"service bottom of stairs">>"Exit/direction signs shall be maintained/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741195851">>"False">>"">>"">>"03/05/2025">>"1013.1">>"Exit signs.">>"">>"Showroom south entrance ">>"Exit/direction signs shall be maintained/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741195918">>"False">>"">>"">>"03/05/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1739549181">>"False">>"Fogo De Chao Brazilian Steakhouse Level 2 B2">>"Fogo De Chao Brazilian Steakhouse Level 2 B2">>"02/14/2025">>"1031.3">>"Obstructions.">>"">>"Exterior exit ramp">>"Means of egress shall be readily accessible
must maintain required egress width">>"Space B2">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739549312">>"False">>"Fogo De Chao Brazilian Steakhouse Level 2 B2">>"Fogo De Chao Brazilian Steakhouse Level 2 B2">>"02/14/2025">>"904.5.1">>"System test.">>"">>"Rotisserie oven">>"Replace missing caps on wet chemical suppression system nozzles/RN">>"Space B2">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739548999">>"False">>"Fogo De Chao Brazilian Steakhouse Level 2 B2">>"Fogo De Chao Brazilian Steakhouse Level 2 B2">>"02/14/2025">>"1031.3">>"Obstructions.">>"">>"Exterior of side dining room exit">>"Means of egress shall be readily accessible">>"Space B2">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739549071">>"False">>"Fogo De Chao Brazilian Steakhouse Level 2 B2">>"Fogo De Chao Brazilian Steakhouse Level 2 B2">>"02/14/2025">>"1031.3">>"Obstructions.">>"">>"Exterior common mall exit corridor">>"Means of egress shall be readily accessible
must maintain required 10 foot egress width">>"Space B2">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739549561">>"False">>"Fogo De Chao Brazilian Steakhouse Level 2 B2">>"Fogo De Chao Brazilian Steakhouse Level 2 B2">>"02/14/2025">>"1031.3">>"Obstructions.">>"">>"party room">>"Means of egress shall be readily accessible
Restores, obstructed by tables and chairs and sofa">>"Space B2">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739550104">>"False">>"Fogo De Chao Brazilian Steakhouse Level 2 B2">>"Fogo De Chao Brazilian Steakhouse Level 2 B2">>"02/14/2025">>"607.3.3.2    ">>"Grease accumulation.   ">>"">>"Rotisserie oven">>"Kitchen hood cleaning required - Grease accumulation removed/RNIncrease cleaning frequency to every two months">>"Space B2">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739550914">>"False">>"Seasons 52">>"Seasons 52">>"02/14/2025">>"703.1">>"Maintaining protection.">>"">>"Kitchen">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"A 14">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739549675">>"False">>"Fogo De Chao Brazilian Steakhouse Level 2 B2">>"Fogo De Chao Brazilian Steakhouse Level 2 B2">>"02/14/2025">>"1013.1">>"Exit signs.">>"">>"Mall seating area">>"Additional exit signage required">>"Space B2">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739550054">>"False">>"Fogo De Chao Brazilian Steakhouse Level 2 B2">>"Fogo De Chao Brazilian Steakhouse Level 2 B2">>"02/14/2025">>"607.3.3.2    ">>"Grease accumulation.   ">>"">>"Rotisserie oven">>"Grease accumulation on cooking appliances shall be removed/RN">>"Space B2">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739548004">>"False">>"Grand Lux Cafe Level 2 R1">>"Grand Lux Cafe Level 2 R1">>"02/14/2025">>"1008.2">>"Illumination required.">>"">>"Women's restroom">>"Emergency egress lighting shall be maintained
Emergency light is missing a lightbulb">>"R 1">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739548052">>"False">>"Grand Lux Cafe Level 2 R1">>"Grand Lux Cafe Level 2 R1">>"02/14/2025">>"1008.2">>"Illumination required.">>"">>"Men's restroom">>"Emergency egress lighting shall be maintained">>"R 1">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739547721">>"False">>"Grand Lux Cafe Level 2 R1">>"Grand Lux Cafe Level 2 R1">>"02/14/2025">>"1008.2">>"Illumination required.">>"">>"Right side of bar">>"Emergency egress lighting shall be maintained
Emergency light is missing a lightbulb">>"R 1">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739547918">>"False">>"Grand Lux Cafe Level 2 R1">>"Grand Lux Cafe Level 2 R1">>"02/14/2025">>"907.8.1">>"Maintenance required.">>"">>"">>"Fire alarm maintenance required/RNFire alarms in trouble and needs to be serviced">>"R 1">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739548111">>"False">>"Grand Lux Cafe Level 2 R1">>"Grand Lux Cafe Level 2 R1">>"02/14/2025">>"1008.2">>"Illumination required.">>"">>"Table 61">>"Emergency egress lighting shall be maintained
Emergency latest missing a lightbulb">>"R 1">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739548406">>"False">>"Grand Lux Cafe Level 2 R1">>"Grand Lux Cafe Level 2 R1">>"02/14/2025">>"904.5.1">>"System test.">>"">>"Previous locations across main cook line">>"Replace missing caps on wet chemical suppression system nozzles/RN">>"R 1">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739548628">>"False">>"Grand Lux Cafe Level 2 R1">>"Grand Lux Cafe Level 2 R1">>"02/14/2025">>"604.10.3">>"Extension cords.">>"">>"Office">>"Space heaters must be plugged directly into a power receptacle ">>"R 1">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739548218">>"False">>"Grand Lux Cafe Level 2 R1">>"Grand Lux Cafe Level 2 R1">>"02/14/2025">>"1008.2">>"Illumination required.">>"">>"Table 102">>"Emergency egress lighting shall be maintained">>"R 1">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739548295">>"False">>"Grand Lux Cafe Level 2 R1">>"Grand Lux Cafe Level 2 R1">>"02/14/2025">>"1008.2">>"Illumination required.">>"">>"soda, machines, left side service station">>"Emergency egress lighting shall be maintained
One light burnt out">>"R 1">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739899413">>"False">>"Stew Leonard's">>"Stew Leonard's">>"02/18/2025">>"904.5.1">>"System test.">>"">>"donut machine">>"Kitchen suppression system inspection report shall be emailed to Fire Prevention/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739900179">>"False">>"Stew Leonard's">>"Stew Leonard's">>"02/18/2025">>"904.5.1">>"System test.">>"">>"All kitchen hoods">>"Wet chemical suppression system inspection required (6 months)/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739899367">>"False">>"Stew Leonard's">>"Stew Leonard's">>"02/18/2025">>"1031.10">>"Emergency lighting equipment inspection and testing.">>"">>"structure">>"Emergency lighting power system shall be tested and report emailed to Fire Prevention/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739899390">>"False">>"Stew Leonard's">>"Stew Leonard's">>"02/18/2025">>"607.3.3">>"Cleaning.">>"">>"donute machine">>"Kitchen exhaust system overdue for 6 month cleaning/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739900310">>"False">>"Stew Leonard's">>"Stew Leonard's">>"02/18/2025">>"607.3.3.2    ">>"Grease accumulation.   ">>"">>"prepared kitchen, above open top grills">>"Grease accumulation on cooking appliances shall be removed/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739900947">>"False">>"Stew Leonard's">>"Stew Leonard's">>"02/18/2025">>"315.3.3">>"Equipment rooms.">>"">>"2nd floor electrical and mechanical room. ">>"Storage not permitted in utility rooms">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739981732">>"False">>"">>"">>"02/19/2025">>"102.1.1">>"">>"">>"Hallway">>"Conditions liable to interfere with egress of occupants or operation of fire department">>"">>"">>"">>"">>"">
"FPVIO-25-1739900339">>"False">>"Stew Leonard's">>"Stew Leonard's">>"02/18/2025">>"607.3.3">>"Cleaning.">>"">>"prepared foods cookline">>"Kitchen exhaust system cleaning required">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739900477">>"False">>"Stew Leonard's">>"Stew Leonard's">>"02/18/2025">>"901.4.1">>"Fire protection systems.">>"">>"prepared food cookline, open top grill/broiler">>"Fire protection system performance shall not be reduced, kitchen suppression nozzles shall be in proper place.">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739551989">>"False">>"Eddie V's Holding LLC">>"Eddie V's Holding LLC">>"02/14/2025">>"1031.3">>"Obstructions.">>"">>"Boh COMMON HALL">>"Means of egress shall be readily accessible">>"A 8A">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739552227">>"False">>"Eddie V's Holding LLC">>"Eddie V's Holding LLC">>"02/14/2025">>"1031.3">>"Obstructions.">>"">>"Boh mall corridor ">>"Means of egress shall be readily accessible">>"A 8A">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739550948">>"False">>"Seasons 52">>"Seasons 52">>"02/14/2025">>"1013.1">>"Exit signs.">>"">>"Kitchen">>"Exit/direction signs shall be maintained/RN">>"A 14">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739551401">>"False">>"Seasons 52">>"Seasons 52">>"02/14/2025">>"1008.2">>"Illumination required.">>"">>"Entrance">>"Emergency egress lighting shall be maintained">>"A 14">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739552268">>"False">>"Eddie V's Holding LLC">>"Eddie V's Holding LLC">>"02/14/2025">>"904.5.1">>"System test.">>"">>"Kitchen">>"Replace missing caps on wet chemical suppression system nozzles/RN">>"A 8A">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739899314">>"False">>"Stew Leonard's">>"Stew Leonard's">>"02/18/2025">>"1203.4.3">>"Records.">>"">>"structure ">>"Annual Emergency Generator inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739899334">>"False">>"Stew Leonard's">>"Stew Leonard's">>"02/18/2025">>"607.3.3.2    ">>"Grease accumulation.   ">>"">>"donut machine">>"Grease accumulation on cooking appliances shall be removed/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739899231">>"False">>"Stew Leonard's">>"Stew Leonard's">>"02/18/2025">>"901.6.3">>"Records.">>"">>"structure">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739899262">>"False">>"Stew Leonard's">>"Stew Leonard's">>"02/18/2025">>"901.6.3">>"Records.">>"">>"structure">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739547645">>"False">>"Grand Lux Cafe Level 2 R1">>"Grand Lux Cafe Level 2 R1">>"02/14/2025">>"907.8.1">>"Maintenance required.">>"">>"Your kitchen hallway, near bakery freezer">>"Fire alarm maintenance required/RN">>"R 1">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-00052">>"False">>"Bounce U">>"Bounce U">>"02/04/2025">>"906.2">>"General requirements.">>"">>"Throughout">>"Fire Extinguisher overdue for maintenance/inspection.">>"Suite 2">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1738778606">>"False">>"">>"">>"02/05/2025">>"906.2">>"General requirements.">>"">>"Throughout Business ">>"Fire extinguishers must be properly unobstructed, serviced and tagged ">>"">>"">>"">>"">>"">
"FPVIO-25-1738264912">>"False">>"">>"">>"01/30/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1738264919">>"False">>"">>"">>"01/30/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1738945399">>"False">>"">>"">>"02/07/2025">>"1008.2">>"Illumination required.">>"">>"exit sign at kitchen exit">>"Emergency egress lighting shall be maintained">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1738945679">>"False">>"">>"">>"02/07/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-00102">>"False">>"Skin Confidence by Kathy">>"Skin Confidence by Kathy">>"02/10/2025">>"604.6">>"Unapproved conditions.">>"">>"Ceiling ">>"Open Electrical Junction boxes / wiring is prohibited/RN">>"Suite 104">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1738945629">>"False">>"">>"">>"02/07/2025">>"901.4.1">>"Fire protection systems.">>"">>"">>"Fire Protection system maintenance required. Fire alarm in alarm ">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1738945671">>"False">>"">>"">>"02/07/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1738263883">>"False">>"Paramus Furniture Liquidators">>"Paramus Furniture Liquidators">>"01/30/2025">>"906.6">>"Unobstructed and unobscured.">>"">>"">>"Fire extinguisher access shall not be obstructed/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1738264083">>"False">>"Paramus Furniture Liquidators">>"Paramus Furniture Liquidators">>"01/30/2025">>"604.4">>"Multiplug adapters.">>"">>"Showroom north East exit">>"Multi-plug adapters prohibied">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1738263597">>"False">>"Paramus Furniture Liquidators">>"Paramus Furniture Liquidators">>"01/30/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1738263813">>"False">>"Paramus Furniture Liquidators">>"Paramus Furniture Liquidators">>"01/30/2025">>"1031.3">>"Obstructions.">>"">>"">>"Means of egress shall not be obstructed">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1738264127">>"False">>"Paramus Furniture Liquidators">>"Paramus Furniture Liquidators">>"01/30/2025">>"906.6">>"Unobstructed and unobscured.">>"">>"showroom North East exit">>"Fire extinguisher access shall not be obstructed/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1738264355">>"False">>"Paramus Furniture Liquidators">>"Paramus Furniture Liquidators">>"01/30/2025">>"1031.3">>"Obstructions.">>"">>"both north exits from clearance area">>"Means of egress shall not be obstructed">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1738264486">>"False">>"Paramus Furniture Liquidators">>"Paramus Furniture Liquidators">>"01/30/2025">>"315.3.3">>"Equipment rooms.">>"">>"Electrical Room">>"Storage not permitted in utility rooms">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1738264166">>"False">>"Paramus Furniture Liquidators">>"Paramus Furniture Liquidators">>"01/30/2025">>"1031.3">>"Obstructions.">>"">>"showroom Northeast exit">>"Means of egress shall not be obstructed">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1738264251">>"False">>"Paramus Furniture Liquidators">>"Paramus Furniture Liquidators">>"01/30/2025">>"315.3.3">>"Equipment rooms.">>"">>"sprinkler room">>"Storage not permitted in utility rooms">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739545821">>"False">>"Pinstripes M17">>"Pinstripes M17">>"02/14/2025">>"1031.3">>"Obstructions.">>"">>"Main electrical room exit into storage">>"Means of egress shall be readily accessible">>"M17">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739545895">>"False">>"Pinstripes M17">>"Pinstripes M17">>"02/14/2025">>"906.2">>"General requirements.">>"">>"Main electrical room">>"Fire extinguisher overdue for maintenance/inspection/RN">>"M17">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739463871">>"False">>"Miller's Ale House">>"Miller's Ale House">>"02/13/2025">>"906.2">>"General requirements.">>"">>"main entrance ">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739464167">>"False">>"Miller's Ale House">>"Miller's Ale House">>"02/13/2025">>"315.3.3">>"Equipment rooms.">>"">>"electrical room">>"Storage not permitted in utility rooms">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739546095">>"False">>"Pinstripes M17">>"Pinstripes M17">>"02/14/2025">>"1008.2">>"Illumination required.">>"">>"First floor, elevator lobby outside of elevator one">>"Emergency egress lighting shall be maintained">>"M17">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739546486">>"False">>"Pinstripes M17">>"Pinstripes M17">>"02/14/2025">>"903.3.3">>"Obstructed locations.">>"">>"Hallway behind sales office, first floor">>"Fire Sprinklers shall not be obstructed by debris/RN">>"M17">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739547578">>"False">>"Grand Lux Cafe Level 2 R1">>"Grand Lux Cafe Level 2 R1">>"02/14/2025">>"5:70-4.9(d)">>"Automatic fire and carbon monoxide alarms">>"">>"Rear hallway for kitchen, near Bakery freezer">>"Carbon Monoxide Detectors shall be maintained/RN">>"R 1">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739546194">>"False">>"Pinstripes M17">>"Pinstripes M17">>"02/14/2025">>"906.9">>"Extinguisher installation.">>"">>"Hallway near bocce first floor">>"Fire extinguisher shall be properly mounted/RN">>"M17">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739546300">>"False">>"Pinstripes M17">>"Pinstripes M17">>"02/14/2025">>"1008.2">>"Illumination required.">>"">>"Bowling lane 10 level one">>"Emergency egress lighting shall be maintained">>"M17">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1739384104">>"False">>"">>"">>"02/12/2025">>"906.2">>"General requirements.">>"">>"Throughout ">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1739384172">>"False">>"">>"">>"02/12/2025">>"1013.1">>"Exit signs.">>"">>"2
by rear emergency exit
by swinging doors to back">>"Exit/direction signs shall be maintained/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1739288855">>"False">>"">>"">>"02/11/2025">>"901.4.1">>"Fire protection systems.">>"">>"">>"Fire Protection system maintenance required/RNFire Alarm must be serviced">>"">>"">>"">>"">>"">
"FPVIO-25-1739297392">>"False">>"">>"">>"02/11/2025">>"1013">>"EXIT SIGNS">>"">>"">>"Repair Exit Sign (Battery Operation)">>"">>"">>"">>"">>"">
"FPVIO-25-1739386202">>"False">>"">>"">>"02/12/2025">>"901.4.1">>"Fire protection systems.">>"">>"Fire alarm trouble ">>"Fire Protection system maintenance required/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1739387210">>"False">>"">>"">>"02/12/2025">>"906.9">>"Extinguisher installation.">>"">>"between detail areas">>"Fire extinguisher shall be properly mounted/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1739387452">>"False">>"">>"">>"02/12/2025">>"604.3.1">>"Labeling.">>"">>"Breakers for testing emergency lighting shall be clearly labeled. ">>"All circuits shall be properly identified in electrical panel/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1739387119">>"False">>"">>"">>"02/12/2025">>"906.2">>"General requirements.">>"">>"throughout ">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1739387163">>"False">>"">>"">>"02/12/2025">>"503.4">>"Obstruction of fire apparatus access roads.">>"">>"VW">>"Fire lane shall not be obstructed">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740069835">>"False">>"The Outlets at Bergen Town Center">>"The Outlets at Bergen Town Center">>"02/20/2025">>"901.4.1">>"Fire protection systems.">>"">>"">>"Fire protection system performance shall not be reduced. Storage within 36" clearance of standpipe connection ">>"Attn; Bassam Mhich, General Manager">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740420832">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"704.2">>"Opening protectives.">>"">>"BOH Abercrombie ">>"Fire doors shall not be blocked open or obstructed">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740420924">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"Stairwell near psycho bunny">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740420533">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"703.1">>"Maintaining protection.">>"">>"BOH H&M">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740420735">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"704.2">>"Opening protectives.">>"">>"BOH Old JCP">>"Fire doors shall not be blocked open or obstructed">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740421207">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"704.2">>"Opening protectives.">>"">>"BOH Gap to old JCP">>"Fire doors shall not be blocked open or obstructed">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740422434">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"BOH Loft">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740422513">>"False">>"">>"">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"Mall corridor ">>"Storage not permitted in means of egress/RN">>"2164">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740421358">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"BOH Adidas">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740421443">>"False">>"">>"">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"Mall corridor ">>"Storage not permitted in means of egress/RN">>"D14">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740419267">>"False">>"">>"">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"">>"Storage not permitted in means of egress/RN">>"2109">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740419502">>"False">>"">>"">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"BOH Mall corridor ">>"Storage not permitted in means of egress/RN">>"2119">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740419105">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"BOH Sam Edelman ">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740419182">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"BOH Nespresso">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740419698">>"False">>"">>"">>"02/24/2025">>"1031.3">>"Obstructions.">>"">>"Rear exit from store">>"Means of egress shall not be obstructed">>"2119">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740420109">>"False">>"">>"">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"Mall corridor ">>"Storage not permitted in means of egress/RN">>"2132">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740420475">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"BOH H&M">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740419953">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"BOH Tesla">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740420044">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"BOH free people">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740425125">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"905.1">>"General.">>"">>"Next to yogy bee">>"Standpipe system shall be maintained/RNCabinet door is unable to be opened. ">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740425205">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"BOH Eddie Vs">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740424874">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"703.1">>"Maintaining protection.">>"">>"BOH EAK Ramen">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740424926">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"403.11.1.5    ">>"Tenant identification.   ">>"">>"Throughout ">>"Tenant identification required/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740425596">>"False">>"">>"">>"02/24/2025">>"605.3">>"Working space and clearance.">>"">>"">>"Minimum clearance to electric service equipment - 36 inch clearance">>"">>"">>"">>"">>"">
"FPVIO-25-1740426032">>"False">>"">>"">>"02/24/2025">>"1010.4">>"Locks permitted.">>"">>"Entrance">>"Unapproved locks shall be removed
Latching gate is not permitted. ">>"2224">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740426278">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"Corridor near level 2 Forever 21">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740425697">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"BOH AMC/Public restrooms ">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740425779">>"False">>"">>"">>"02/24/2025">>"102.1.1">>"">>"">>"">>"Remove all storage from rear exit vestibule.">>"">>"">>"">>"">>"">
"FPVIO-25-1740423118">>"False">>"">>"">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"Mall corridor ">>"Storage not permitted in means of egress/RN">>"1046, S1080, S1033">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740423189">>"False">>"">>"">>"02/24/2025">>"1031.3">>"Obstructions.">>"">>"Sales fool or exit level 2">>"Means of egress shall not be obstructed">>"1046, S1080, S1033">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740423019">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"BOH Zara level 2">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740423084">>"False">>"">>"">>"02/24/2025">>"1031.3">>"Obstructions.">>"">>"Mall corridor ">>"Means of egress shall not be obstructed">>"1046, S1080, S1033">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740423515">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"509.1">>"Identification.">>"">>"Throughout ">>"Fire Department access and identification required
Electrical and Sprinkler Rooms need to be properly identified/labeled">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740424486">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"BOH Vans">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740424529">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"BOH Kura Sushi">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740423650">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"Mall management corridor ">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740424432">>"False">>"Westfield Garden State Plaza">>"Westfield Garden State Plaza">>"02/24/2025">>"1031.1.1">>"Storage.">>"">>"BOH Madison Reed">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740418459">>"False">>"">>"">>"02/24/2025">>"901.4.1">>"Fire protection systems.">>"">>"soffit in canopy outside of vacant space 38">>"Fire Protection system maintenance required, sprinkler heads shall be in proper orientation.">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740078591">>"False">>"">>"">>"02/20/2025">>"1203.4.3">>"Records.">>"">>"">>"Annual Emergency Generator inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1740079539">>"False">>"">>"">>"02/20/2025">>"315.3">>"Storage in buildings.">>"">>"Upstairs storage ">>"Storage shall be neat and orderly./CRMust maintain 36 inch aisle.
Storage should not block emergency light.">>"">>"">>"">>"">>"">
"FPVIO-25-1740078497">>"False">>"">>"">>"02/20/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1740078586">>"False">>"">>"">>"02/20/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1740079769">>"False">>"">>"">>"02/20/2025">>"906.6">>"Unobstructed and unobscured.">>"">>"Upstairs storage">>"Fire extinguisher access shall not be obstructed/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1740141843">>"False">>"">>"">>"02/21/2025">>"703.1">>"Maintaining protection.">>"">>"bh2">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1740144424">>"False">>"The Outlets at Bergen Town Center">>"The Outlets at Bergen Town Center">>"02/21/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"Attn; Bassam Mhich, General Manager">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740079929">>"False">>"">>"">>"02/20/2025">>"906.2">>"General requirements.">>"">>"Upstairs storage & rim shop">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1740080265">>"False">>"">>"">>"02/20/2025">>"1008.2">>"Illumination required.">>"">>"wash bay">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1740071963">>"False">>"The Outlets at Bergen Town Center">>"The Outlets at Bergen Town Center">>"02/20/2025">>"704.2">>"Opening protectives.">>"">>"corridor 5 lower near trash dock 1 ">>"Fire doors shall not be blocked open or obstructed">>"Attn; Bassam Mhich, General Manager">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740072001">>"False">>"The Outlets at Bergen Town Center">>"The Outlets at Bergen Town Center">>"02/20/2025">>"906.9">>"Extinguisher installation.">>"">>"corridor 5 Lower level near trash dock 1">>"Fire extinguisher shall be properly mounted/RN">>"Attn; Bassam Mhich, General Manager">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740070335">>"False">>"The Outlets at Bergen Town Center">>"The Outlets at Bergen Town Center">>"02/20/2025">>"1031.3">>"Obstructions.">>"">>"Upper Corridor 2 adjacent to Fire Command Room">>"Means of egress shall not be obstructed">>"Attn; Bassam Mhich, General Manager">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740071429">>"False">>"The Outlets at Bergen Town Center">>"The Outlets at Bergen Town Center">>"02/20/2025">>"1013.1">>"Exit signs.">>"">>"corridor 2 lower level between old navy and h&m">>"Exit/direction signs shall be maintained/RN">>"Attn; Bassam Mhich, General Manager">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740073438">>"False">>"The Valley Hospital">>"The Valley Hospital">>"02/20/2025">>"607.1">>"General.">>"">>"kitchen">>"Kitchen exhaust hood system maintenance required, make up air needs to be balanced for kitchen exhaust. ">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740077174">>"False">>"">>"">>"02/20/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1740077182">>"False">>"">>"">>"02/20/2025">>"1203.4.3">>"Records.">>"">>"">>"Annual Emergency Generator inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1740076709">>"False">>"">>"">>"02/20/2025">>"1008.2">>"Illumination required.">>"">>"throughout sales floor ">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1740077167">>"False">>"">>"">>"02/20/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1740412276">>"False">>"">>"">>"02/24/2025">>"610.1">>"General.">>"">>"South East Sales">>"Repair emergency light ">>"">>"">>"">>"">>"">
"FPVIO-25-1740412326">>"False">>"">>"">>"02/24/2025">>"610.1">>"General.">>"">>"SE Exit">>"Repair Emergency Light">>"">>"">>"">>"">>"">
"FPVIO-25-1740411639">>"False">>"On The Border #0061">>"On The Border #0061">>"02/24/2025">>"1008.2">>"Illumination required.">>"">>"Women's room">>"Emergency egress lighting shall be maintained">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740412165">>"False">>"">>"">>"02/24/2025">>"610.1">>"General.">>"">>"1st floor center sales">>"Repair emergency light">>"">>"">>"">>"">>"">
"FPVIO-25-1740412374">>"False">>"">>"">>"02/24/2025">>"1013">>"EXIT SIGNS">>"">>"Main Exit">>"Repair Exit Light (Battery Operation)">>"">>"">>"">>"">>"">
"FPVIO-25-1740412671">>"False">>"">>"">>"02/24/2025">>"610.1">>"General.">>"">>"2nd floor SE Sales">>"Repair emergency light">>"">>"">>"">>"">>"">
"FPVIO-25-1740418301">>"False">>"">>"">>"02/24/2025">>"1010.4">>"Locks permitted.">>"">>"parking deck, mechanical penthouse.">>"Unapproved locks shall be removed, slide bolt and pad lock shall be removed. ">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1740412453">>"False">>"">>"">>"02/24/2025">>"610.1">>"General.">>"">>"NE Sales Floor">>"Repair emergency light">>"">>"">>"">>"">>"">
"FPVIO-25-1740412524">>"False">>"">>"">>"02/24/2025">>"610.1">>"General.">>"">>"1st floor sales by stairs">>"Repair emergency light (2)">>"">>"">>"">>"">>"">
"FPVIO-25-1740409658">>"False">>"Capital Grille G02">>"Capital Grille G02">>"02/24/2025">>"1031.10">>"Emergency lighting equipment inspection and testing.">>"">>"stairwell">>"emergency lighting needs to be serviced">>"G 02">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740409896">>"False">>"Capital Grille G02">>"Capital Grille G02">>"02/24/2025">>"1031.10">>"Emergency lighting equipment inspection and testing.">>"">>"Table 7">>"emergency light needs to be serviced">>"G 02">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740144444">>"False">>"The Outlets at Bergen Town Center">>"The Outlets at Bergen Town Center">>"02/21/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"Attn; Bassam Mhich, General Manager">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740409384">>"False">>"Capital Grille G02">>"Capital Grille G02">>"02/24/2025">>"604.3">>"Working space and clearance.">>"">>"Electrical Room">>"Storage is not permitted in electrical rooms">>"G 02">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740409991">>"False">>"Capital Grille G02">>"Capital Grille G02">>"02/24/2025">>"1031.10">>"Emergency lighting equipment inspection and testing.">>"">>"Hallway">>"emergency needs to be serviced">>"G 02">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740411345">>"False">>"On The Border #0061">>"On The Border #0061">>"02/24/2025">>"1008.2">>"Illumination required.">>"">>"Rear exit from kitchen">>"Emergency egress lighting shall be maintained">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740411476">>"False">>"On The Border #0061">>"On The Border #0061">>"02/24/2025">>"607.3.3.2    ">>"Grease accumulation.   ">>"">>"">>"Kitchen hood cleaning required - Grease accumulation removed/RNGrease cleaning frequency for broiler hood needs to be increased to every two months">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740410064">>"False">>"Capital Grille G02">>"Capital Grille G02">>"02/24/2025">>"1031.10">>"Emergency lighting equipment inspection and testing.">>"">>"Table 71">>"emergency light needs to be serviced">>"G 02">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1740410116">>"False">>"Capital Grille G02">>"Capital Grille G02">>"02/24/2025">>"1031.10">>"Emergency lighting equipment inspection and testing.">>"">>"Table 51">>"needs to be serviced">>"G 02">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742393255">>"False">>"">>"">>"03/19/2025">>"1013">>"EXIT SIGNS">>"">>"1st floor hallway">>"Repair Exit Light (Battery Operation)">>"">>"">>"">>"">>"">
"FPVIO-25-1742917031">>"False">>"">>"">>"03/25/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742922359">>"False">>"">>"">>"03/25/2025">>"1013.1">>"Exit signs.">>"">>"">>"Exit/direction signs shall be maintained/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742393206">>"False">>"">>"">>"03/19/2025">>"610.1">>"General.">>"">>"1st floor hallway">>"Repair Emergency Light">>"">>"">>"">>"">>"">
"FPVIO-25-1742396170">>"False">>"">>"">>"03/19/2025">>"906.2">>"General requirements.">>"">>"Throughout">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742396451">>"False">>"">>"">>"03/19/2025">>"906.2">>"General requirements.">>"">>"Throughout">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742395887">>"False">>"">>"">>"03/19/2025">>"906.2">>"General requirements.">>"">>"Throughout">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742395995">>"False">>"">>"">>"03/19/2025">>"1013.1">>"Exit signs.">>"">>"Rear Exit">>"Exit/direction signs shall be maintained/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742923335">>"False">>"">>"">>"03/25/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742923145">>"False">>"">>"">>"03/25/2025">>"1010.4">>"Locks permitted.">>"">>"">>"Unapproved locks shall be removed">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742923640">>"False">>"">>"">>"03/25/2025">>"1031.3">>"Obstructions.">>"">>"">>"Means of egress shall not be obstructed">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742322360">>"False">>"">>"">>"03/18/2025">>"906.2">>"General requirements.">>"">>"Laundry room">>"Fire extinguisher overdue for maintenance/inspection/RN">>"B1 & B2">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742922608">>"False">>"">>"">>"03/25/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742922532">>"False">>"">>"">>"03/25/2025">>"1010.1.9">>"Door operations.">>"">>"Emergency exit off sales floor">>"Means of egress shall be readily openable">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742923034">>"False">>"">>"">>"03/25/2025">>"703.1">>"Maintaining protection.">>"">>"">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742922629">>"False">>"">>"">>"03/25/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742486150">>"False">>"">>"">>"03/20/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742486944">>"False">>"">>"">>"03/20/2025">>"906.2">>"General requirements.">>"">>"all gas pumps
">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742485772">>"False">>"">>"">>"03/20/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742917023">>"False">>"">>"">>"03/25/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742488016">>"False">>"">>"">>"03/20/2025">>"1013.1">>"Exit signs.">>"">>"back west stairwell ">>"Exit/direction signs shall be maintained/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742488093">>"False">>"">>"">>"03/20/2025">>"1008.2">>"Illumination required.">>"">>"back west stairwell both lights ">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1742487041">>"False">>"">>"">>"03/20/2025">>"604.3">>"Working space and clearance.">>"">>"stock room">>"Storage not permitted within 36 inches of electrical service equipment">>"">>"">>"">>"">>"">
"FPVIO-25-1742487116">>"False">>"">>"">>"03/20/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742483705">>"False">>"">>"">>"03/20/2025">>"605.4.2">>"Power supply.">>"">>"">>"Power strips must not be piggy backed">>"">>"">>"New Jersey">>"">>"">
"FPVIO-25-1742484203">>"False">>"">>"">>"03/20/2025">>"604.5">>"Extension cords.">>"">>"">>"Extension cords shall not be utilized for permanent wiring">>"">>"">>"New Jersey">>"">>"">
"FPVIO-25-1742396474">>"False">>"">>"">>"03/19/2025">>"1013.1">>"Exit signs.">>"">>"south exit door">>"Exit/direction signs shall be maintained/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742397745">>"False">>"">>"">>"03/19/2025">>"1008.2">>"Illumination required.">>"">>"Throughout retail floor">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1742485612">>"False">>"">>"">>"03/20/2025">>"703.1">>"Maintaining protection.">>"">>"rear near toys">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742485768">>"False">>"">>"">>"03/20/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742485534">>"False">>"">>"">>"03/20/2025">>"703.1">>"Maintaining protection.">>"">>"ceiling near bedding">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742485573">>"False">>"">>"">>"03/20/2025">>"1008.2">>"Illumination required.">>"">>"rear wall by suitcases ">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1742312809">>"False">>"T. S. Jewelry aka Tam Jewelry">>"T. S. Jewelry aka Tam Jewelry">>"03/18/2025">>"5:70-2.7(a)">>"Permits required">>"">>"">>"Type 1 torch permit required/RN">>"Booth 26">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742312993">>"False">>"Cavas Jewelry">>"Cavas Jewelry">>"03/18/2025">>"906.2">>"General requirements.">>"">>"">>"Fire extinguisher overdue for maintenance/inspection/RN">>"Booth 3">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742312222">>"False">>"Dona Bona Jewelry - Booth 5">>"Dona Bona Jewelry - Booth 5">>"03/18/2025">>"5:70-2.7(a)">>"Permits required">>"">>"">>"Type 1 torch permit required/RN">>"Booth 5">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742312378">>"False">>"Jam's Jewelry, LLC - Booth 11">>"Jam's Jewelry, LLC - Booth 11">>"03/18/2025">>"5:70-2.7(a)">>"Permits required">>"">>"">>"Type 1 torch permit required/RN">>"Booth 11">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742313211">>"False">>"Asmond Jewelry">>"Asmond Jewelry">>"03/18/2025">>"5:70-2.7(a)">>"Permits required">>"">>"">>"Type 1 torch permit required/RN">>"Booth 23">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742313466">>"False">>"Paramus Jewelry Exchange LLC">>"Paramus Jewelry Exchange LLC">>"03/18/2025">>"1013.1">>"Exit signs.">>"">>"west most entrance ">>"Exit/direction signs shall be maintained/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742313026">>"False">>"Cavas Jewelry">>"Cavas Jewelry">>"03/18/2025">>"5:70-2.7(a)">>"Permits required">>"">>"">>"Type 1 torch permit required/RN">>"Booth 3">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742313195">>"False">>"Asmond Jewelry">>"Asmond Jewelry">>"03/18/2025">>"906.2">>"General requirements.">>"">>"">>"Fire extinguisher overdue for maintenance/inspection/RN">>"Booth 23">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742308367">>"False">>"">>"">>"03/18/2025">>"1013">>"EXIT SIGNS">>"">>"NW Hallway">>"Repair Exit Light (Battery Operation)">>"">>"">>"">>"">>"">
"FPVIO-25-1743086689">>"False">>"">>"">>"03/27/2025">>"906.9">>"Extinguisher installation.">>"">>"Front of store by roaster">>"Fire extinguisher shall be properly mounted/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742308198">>"False">>"">>"">>"03/18/2025">>"1013">>"EXIT SIGNS">>"">>"Hallway">>"Repair Exit Light (Battery Operation)">>"">>"">>"">>"">>"">
"FPVIO-25-1742308239">>"False">>"">>"">>"03/18/2025">>"1013">>"EXIT SIGNS">>"">>"Hallway above break room door">>"Repair Exit Light (Battery Operation)">>"">>"">>"">>"">>"">
"FPVIO-25-1742309401">>"False">>"">>"">>"03/18/2025">>"1013">>"EXIT SIGNS">>"">>"Hallway by receptionist ">>"Repair Exit Light (Battery Operation)">>"">>"">>"">>"">>"">
"FPVIO-25-1743086526">>"False">>"">>"">>"03/27/2025">>"1013.3">>"Mistaken egress.">>"">>"">>"Mistaken egress prohibited. Exit sign above electrical room must be removed.">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1743086594">>"False">>"">>"">>"03/27/2025">>"604.3.1">>"Labeling.">>"">>"Electrical Room">>"Panel Labeling is inconsistent, Panel must be labeled with proper labels
">>"">>"">>"">>"">>"">
"FPVIO-25-1743086591">>"False">>"">>"">>"03/27/2025">>"703.1">>"Maintaining protection.">>"">>"">>"Holes in fire rated walls/ceilings shall be repaired. Ceiling tiles must be put back in place. ">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742322137">>"False">>"">>"">>"03/18/2025">>"703.1">>"Maintaining protection.">>"">>"">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"B1 & B2">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1743014294">>"False">>"">>"">>"03/26/2025">>"1008.2">>"Illumination required.">>"">>"Sales floor">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1743085241">>"False">>"">>"">>"03/27/2025">>"604.3">>"Working space and clearance.">>"">>"Electrical Room">>"Storage not permitted within 36 inches of electrical service equipment">>"1006">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742923832">>"False">>"">>"">>"03/25/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1743013501">>"False">>"">>"">>"03/26/2025">>"1008.2">>"Illumination required.">>"">>"Sales floor">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1743013433">>"False">>"">>"">>"03/26/2025">>"1008.2">>"Illumination required.">>"">>"Backroom">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1743014149">>"False">>"">>"">>"03/26/2025">>"703.1">>"Maintaining protection.">>"">>"Backroom">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743014061">>"False">>"">>"">>"03/26/2025">>"604.3">>"Working space and clearance.">>"">>"Backroom">>"Storage not permitted within 36 inches of electrical service equipment">>"">>"">>"">>"">>"">
"FPVIO-25-1742316623">>"False">>"Paramus Jewelry Exchange LLC">>"Paramus Jewelry Exchange LLC">>"03/18/2025">>"906.9">>"Extinguisher installation.">>"">>"">>"Fire extinguisher shall be properly mounted/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743086448">>"False">>"">>"">>"03/27/2025">>"604.3.1">>"Labeling.">>"">>"Door to Electrical Room">>"Electrical room shall be clearly identified (Signage Required)/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742313598">>"False">>"Paramus Jewelry Exchange LLC">>"Paramus Jewelry Exchange LLC">>"03/18/2025">>"1008.2">>"Illumination required.">>"">>"">>"Emergency egress lighting shall be maintained">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742316581">>"False">>"Paramus Jewelry Exchange LLC">>"Paramus Jewelry Exchange LLC">>"03/18/2025">>"703.1">>"Maintaining protection.">>"">>"">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743085730">>"False">>"">>"">>"03/27/2025">>"906.9">>"Extinguisher installation.">>"">>"Near electrical panel">>"Fire extinguisher shall be properly mounted/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743085632">>"False">>"">>"">>"03/27/2025">>"1031.1.1">>"Storage.">>"">>"Back Exit">>"Storage not permitted in means of egress/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743086339">>"False">>"">>"">>"03/27/2025">>"604.3">>"Working space and clearance.">>"">>"Electrical Room">>"Storage not permitted within 36 inches of electrical service equipment">>"">>"">>"">>"">>"">
"FPVIO-25-1743085857">>"False">>"">>"">>"03/27/2025">>"604.6">>"Unapproved conditions.">>"">>"Stock Room">>"Open Electrical Junction boxes / wiring is prohibited/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742914780">>"False">>"">>"">>"03/25/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"Common Area">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742914723">>"False">>"">>"">>"03/25/2025">>"1031.6">>"Exterior egress.">>"">>"">>"Exterior egress shall not be deteriorated (fire escape and stairs)">>"Common Area">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742915783">>"False">>"">>"">>"03/25/2025">>"906.2">>"General requirements.">>"">>"throughout ">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742914794">>"False">>"">>"">>"03/25/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"Common Area">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-00125">>"False">>"Ozzie's Barber Spa Level 2 L07C">>"Ozzie's Barber Spa Level 2 L07C">>"03/24/2025">>"906.2">>"General requirements.">>"">>"Store">>"Fire extinguisher overdue for maintenance/inspection/RN">>"L 07C">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-00126">>"False">>"Ozzie's Barber Spa Level 2 L07C">>"Ozzie's Barber Spa Level 2 L07C">>"03/24/2025">>"1031.10">>"Emergency lighting equipment inspection and testing.">>"">>"Throughout Store ">>"Emergency lighting power system shall be tested and report emailed to Fire Prevention/RN">>"L 07C">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-00123">>"False">>"Honey Birdette Level 2 L07">>"Honey Birdette Level 2 L07">>"03/24/2025">>"1031.10">>"Emergency lighting equipment inspection and testing.">>"">>"Electric Panel ">>"Emergency lighting power system shall be labeled on the Eectric Panel ">>"Space L07">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-00124">>"False">>"Honey Birdette Level 2 L07">>"Honey Birdette Level 2 L07">>"03/24/2025">>"1031.10.2">>"Power in accordance with the original approval test.">>"">>"Store ">>"Battery-powered emergency lighting equipment shall be tested annually provide report">>"Space L07">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743003036">>"False">>"">>"">>"03/26/2025">>"906.6">>"Unobstructed and unobscured.">>"">>"Storage area">>"Fire extinguisher access shall not be obstructed/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742916970">>"False">>"">>"">>"03/25/2025">>"1008.2">>"Illumination required.">>"">>"Second floor over staircase">>"Emergency egress lighting shall be maintained">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-00117">>"False">>"DCH Paramus Honda Service Station">>"19 Mackay Avenue">>"03/22/2025">>"907.8.1">>"Maintenance required.">>"">>"">>"Fire alarm maintenance required/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743003109">>"False">>"">>"">>"03/26/2025">>"1031.1.1">>"Storage.">>"">>"Aisle towards storage exit">>"Storage not permitted in means of egress/RN">>"">>"">>"">>"">>"">
"FPVIO-25-00119">>"False">>"">>"">>"03/24/2025">>"906.2">>"General requirements.">>"">>"Store ">>"Service Fire Extinguisher ">>"">>"">>"New Jersey">>"">>"">
"FPVIO-25-1742916370">>"False">>"">>"">>"03/25/2025">>"1010.1.9">>"Door operations.">>"">>"side exit off of sales floor">>"Means of egress shall be readily openable">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742916679">>"False">>"">>"">>"03/25/2025">>"1010.1.9">>"Door operations.">>"">>"Rear exit by seamstress area">>"Means of egress shall be readily openable">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-00118">>"False">>"">>"">>"03/24/2025">>"1031.10">>"Emergency lighting equipment inspection and testing.">>"">>"Room 4 & Main Entrance ">>"Service Emergency Lights not working ">>"">>"">>"New Jersey">>"">>"">
"FPVIO-25-1742829668">>"False">>"">>"">>"03/24/2025">>"1013">>"EXIT SIGNS">>"">>"Receptionist ">>"Repair Exit Light (Battery Operation)">>"">>"">>"">>"">>"">
"FPVIO-25-1742829941">>"False">>"">>"">>"03/24/2025">>"610.1">>"General.">>"">>"Stairs">>"Repair Emergency Light ">>"">>"">>"">>"">>"">
"FPVIO-25-1742828011">>"False">>"">>"">>"03/24/2025">>"901.6">>"Inspection, testing and maintenance, any installed.">>"">>"">>"Forward a current copy of the Fire Alarm Inspection Report to this office">>"">>"">>"">>"">>"">
"FPVIO-25-1742828361">>"False">>"">>"">>"03/24/2025">>"610.1">>"General.">>"">>"office">>"Repair Emergency Light">>"">>"">>"">>"">>"">
"FPVIO-25-1742834454">>"False">>"">>"">>"03/24/2025">>"1008.2">>"Illumination required.">>"">>"near bathroom">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1742839358">>"False">>"">>"">>"03/24/2025">>"903.5">>"Testing and maintenance.">>"">>"Throughout Building ">>"Automatic Sprinkler System - must be inspected and tested per NFPA 25 - reports must be submitted">>"">>"">>"">>"">>"">
"FPVIO-25-1742834081">>"False">>"">>"">>"03/24/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743002971">>"False">>"">>"">>"03/26/2025">>"1008.2">>"Illumination required.">>"">>"Storage room">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-00129">>"False">>"Slate">>"165 E. Route 4">>"03/24/2025">>"1031.3">>"Obstructions.">>"">>"front hallway">>"Means of egress shall not be obstructed. All obsructions must be removed.">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-00130">>"False">>"Slate">>"165 E. Route 4">>"03/24/2025">>"906.2">>"General requirements.">>"">>"Throughout">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-00127">>"False">>"Raymour & Flanigan Outlet">>"165 E. Route 4">>"03/24/2025">>"5:70-2.16(b)">>"Imminent hazards">>"">>"Rear exit corridor. Door to exterior stuck shut. Must be made openable immediately">>"IMMINENT HAZARD- Locking or Blocking of any means of egress">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-00128">>"False">>"Slate">>"165 E. Route 4">>"03/24/2025">>"1031.3">>"Obstructions.">>"">>"hallway for rear exit">>"Means of egress shall not be obstructed. All obsructions must be removed.">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-00132">>"False">>"Panera Bread">>"165 E. Route 4">>"03/24/2025">>"1013.1">>"Exit signs.">>"">>"Rear exit from kitchen">>"Exit/direction signs shall be maintained/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742827999">>"False">>"">>"">>"03/24/2025">>"903.5">>"Testing and maintenance.">>"">>"">>"Automatic Sprinkler System - must be inspected and tested per NFPA 25 - reports must be submitted">>"">>"">>"">>"">>"">
"FPVIO-25-1742913885">>"False">>"">>"">>"03/25/2025">>"906.1">>"Where required.">>"">>"Front of the sales floor.">>"Fire Extinguisher required. Install ABC Dry Chemical Fire Extinguisher">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-00131">>"False">>"Panera Bread">>"165 E. Route 4">>"03/24/2025">>"1008.2">>"Illumination required.">>"">>"Front of store">>"Emergency egress lighting shall be maintained">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742488804">>"False">>"">>"">>"03/20/2025">>"509.2">>"Equipment access.">>"">>"sprinkler room">>"Access to utilities and/or building controls shall not be obstructed/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742488806">>"False">>"">>"">>"03/20/2025">>"1013.1">>"Exit signs.">>"">>"all exit stairwells and halls">>"Exit/direction signs shall be maintained/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743011948">>"False">>"">>"">>"03/26/2025">>"1031.1.1">>"Storage.">>"">>"Backroom ">>"Storage not permitted in means of egress/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742488786">>"False">>"">>"">>"03/20/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742490357">>"False">>"">>"">>"03/20/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742490363">>"False">>"">>"">>"03/20/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742489524">>"False">>"">>"">>"03/20/2025">>"703.1">>"Maintaining protection.">>"">>"">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742489842">>"False">>"">>"">>"03/20/2025">>"906.2">>"General requirements.">>"">>"Throughout">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742488584">>"False">>"">>"">>"03/20/2025">>"1031.1">>"General.">>"">>"office emergency exit stairwell , both rails ">>"Means of Egress shall be maintained at all times">>"">>"">>"">>"">>"">
"FPVIO-25-1742488716">>"False">>"">>"">>"03/20/2025">>"906.2">>"General requirements.">>"">>"throughout ">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742488337">>"False">>"">>"">>"03/20/2025">>"1013.1">>"Exit signs.">>"">>"">>"Exit/direction signs shall be maintained/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742488525">>"False">>"">>"">>"03/20/2025">>"1008.2">>"Illumination required.">>"">>"office emergency exit stairwell ">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1743012371">>"False">>"">>"">>"03/26/2025">>"1008.2">>"Illumination required.">>"">>"Backroom">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1742488780">>"False">>"">>"">>"03/20/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743013304">>"False">>"">>"">>"03/26/2025">>"604.3">>"Working space and clearance.">>"">>"Backroom">>"Storage not permitted within 36 inches of electrical service equipment">>"">>"">>"">>"">>"">
"FPVIO-25-1742488747">>"False">>"">>"">>"03/20/2025">>"901.4.1">>"Fire protection systems.">>"">>"fire alarm ">>"Fire Protection system maintenance required. fire alarm trouble">>"">>"">>"">>"">>"">
"FPVIO-25-1742570765">>"False">>"">>"">>"03/21/2025">>"1031.3">>"Obstructions.">>"">>"strip mall common area">>"Means of egress shall not be obstructed">>"">>"">>"">>"">>"">
"FPVIO-25-1742573142">>"False">>"">>"">>"03/21/2025">>"1031.1.1">>"Storage.">>"">>"strip mall common area and loading dock">>"Storage not permitted in means of egress/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743006088">>"False">>"">>"">>"03/26/2025">>"906.2">>"General requirements.">>"">>"">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742569102">>"False">>"">>"">>"03/21/2025">>"1031.1.1">>"Storage.">>"">>"strip mall loading dock and corridor ">>"Storage not permitted in means of egress/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742575532">>"False">>"">>"">>"03/21/2025">>"907.8.1">>"Maintenance required.">>"">>"">>"Fire alarm maintenance required/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742575916">>"False">>"">>"">>"03/21/2025">>"907.8.1">>"Maintenance required.">>"">>"">>"Fire alarm maintenance required/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742573203">>"False">>"">>"">>"03/21/2025">>"907.8.1">>"Maintenance required.">>"">>"strip mall common area">>"Fire alarm maintenance required. Pull station damaged ">>"">>"">>"">>"">>"">
"FPVIO-25-1742573254">>"False">>"">>"">>"03/21/2025">>"1008.2">>"Illumination required.">>"">>"strip mall common area and loading dock">>"Emergency egress lighting shall be maintained.. no power to exit and emergency lights">>"">>"">>"">>"">>"">
"FPVIO-25-1742498167">>"False">>"">>"">>"03/20/2025">>"906.2">>"General requirements.">>"">>"pumps">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742567110">>"False">>"">>"">>"03/21/2025">>"906.2">>"General requirements.">>"">>"Throughout">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742490367">>"False">>"">>"">>"03/20/2025">>"604.3.1">>"Labeling.">>"">>"">>"All circuits shall be properly identified in electrical panel, specifically emergency lighting ">>"">>"">>"">>"">>"">
"FPVIO-25-1743011901">>"False">>"">>"">>"03/26/2025">>"1013.1">>"Exit signs.">>"">>"sales floor">>"Exit/direction signs shall be maintained/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743011562">>"False">>"">>"">>"03/26/2025">>"1008.2">>"Illumination required.">>"">>"Exit in Backroom">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1743006579">>"False">>"">>"">>"03/26/2025">>"1031.10">>"Emergency lighting equipment inspection and testing.">>"">>"Throughout Store">>"Emergency lighting power system shall be tested and report emailed to Fire Prevention/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743011707">>"False">>"">>"">>"03/26/2025">>"1013.1">>"Exit signs.">>"">>"Sales floor">>"Exit/direction signs shall be maintained/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743011598">>"False">>"">>"">>"03/26/2025">>"604.3.1">>"Labeling.">>"">>"">>"Electrical room shall be clearly identified (Signage Required)/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741879925">>"False">>"Prestige Diamond & Time Pieces">>"Prestige Diamond & Time Pieces">>"03/13/2025">>"5:70-2.7(a)">>"Permits required">>"">>"">>"Type 1 torch permit required/RN">>"Booth 32">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742997919">>"False">>"">>"">>"03/26/2025">>"906.2">>"General requirements.">>"">>"1st floor entrance near Nordstrom ">>"Fire extinguisher overdue for maintenance/inspection/RN">>"1046, S1080, S1033">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742998321">>"False">>"">>"">>"03/26/2025">>"604.3">>"Working space and clearance.">>"">>"Electrical Room">>"Storage not permitted within 36 inches of electrical service equipment">>"">>"">>"">>"">>"">
"FPVIO-25-1741880356">>"False">>"Jewelry Center LLC">>"Jewelry Center LLC">>"03/13/2025">>"1013.1">>"Exit signs.">>"">>"Side entrance east side">>"Exit/direction signs shall be maintained/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742997541">>"False">>"">>"">>"03/26/2025">>"604.3">>"Working space and clearance.">>"">>"Electrical Room">>"Storage not permitted within 36 inches of electrical service equipment">>"1046, S1080, S1033">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741880390">>"False">>"Jewelry Center LLC">>"Jewelry Center LLC">>"03/13/2025">>"1013.1">>"Exit signs.">>"">>"Front entrance east side">>"Exit/direction signs shall be maintained/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742997720">>"False">>"">>"">>"03/26/2025">>"1031.1.1">>"Storage.">>"">>"2nd floor exit next to cash registers">>"Storage not permitted in means of egress/RN">>"1046, S1080, S1033">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741879196">>"False">>"Manny's Jewelry">>"Manny's Jewelry">>"03/13/2025">>"5:70-2.7(a)">>"Permits required">>"">>"">>"Type 1 torch permit required/RN">>"Booth 37">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743001678">>"False">>"">>"">>"03/26/2025">>"604.5">>"Extension cords.">>"">>"Register area">>"Extension cords shall not be utilized for permanent wiring">>"">>"">>"">>"">>"">
"FPVIO-25-1741878139">>"False">>"Louis Jewelers - Booth 3A">>"Louis Jewelers - Booth 3A">>"03/13/2025">>"5:70-2.7(a)">>"Permits required">>"">>"">>"Type 1 torch permit required/RN">>"Booth 3A">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-00111">>"False">>"Chrysler Jeep Dodge">>"Chrysler Jeep Dodge">>"03/13/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"Attn. David Porter">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743001727">>"False">>"">>"">>"03/26/2025">>"604.5">>"Extension cords.">>"">>"break room">>"Extension cords shall not be utilized for permanent wiring">>"">>"">>"">>"">>"">
"FPVIO-25-1742998347">>"False">>"">>"">>"03/26/2025">>"604.3.1">>"Labeling.">>"">>"">>"Electrical room shall be clearly identified (Signage Required)/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743180367">>"False">>"">>"">>"03/28/2025">>"1008.2">>"Illumination required.">>"">>"First floor hallway ">>"Emergency egress lighting shall be maintained">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742998395">>"False">>"">>"">>"03/26/2025">>"906.6">>"Unobstructed and unobscured.">>"">>"Near electrical panel">>"Fire extinguisher access shall not be obstructed/RN">>"">>"">>"">>"">>"">
"FPVIO-25-00141">>"False">>"">>"">>"03/26/2025">>"311.2.3">>"Fire separation.">>"">>"Stockroom 3M">>"">>"One Garden State Plaza">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1743179558">>"False">>"">>"">>"03/28/2025">>"1008.2">>"Illumination required.">>"">>"Hallway, fourth floor across from elevator ">>"Emergency egress lighting shall be maintained">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741880540">>"False">>"Jewelry Center LLC">>"Jewelry Center LLC">>"03/13/2025">>"1013.1">>"Exit signs.">>"">>"Front entrance west side">>"Exit/direction signs shall be maintained/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743179649">>"False">>"">>"">>"03/28/2025">>"1008.2">>"Illumination required.">>"">>"north stairwell between 3 and 4">>"Emergency egress lighting shall be maintained">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1743177093">>"False">>"">>"">>"03/28/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742928992">>"False">>"">>"">>"03/25/2025">>"906.2">>"General requirements.">>"">>"Throughout">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743177076">>"False">>"">>"">>"03/28/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742930430">>"False">>"">>"">>"03/25/2025">>"315.3.1">>"Ceiling clearance.">>"">>"">>"Storage shall not be within 24 inches of non-sprinklered building/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743180225">>"False">>"">>"">>"03/28/2025">>"1008.2">>"Illumination required.">>"">>"Fourth floor hallway, outside Suite 401">>"Emergency egress lighting shall be maintained">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-00138">>"False">>"Nordstrom 0060">>"Westfield Garden State Plaza Attn. Bldg Services">>"03/26/2025">>"607.3.3.1.1">>"Cleaning schedule.">>"">>"Restaurant Kitchen">>"Provide Kitchen System Cleaning Report ">>"One Garden State Plaza">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1741880461">>"False">>"Jewelry Center LLC">>"Jewelry Center LLC">>"03/13/2025">>"1013.1">>"Exit signs.">>"">>"Front entrance center, both doors">>"Exit/direction signs shall be maintained/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-00140">>"False">>"">>"">>"03/26/2025">>"607.1">>"General.">>"">>"Restaurant Kitchen">>"Kitchen exhaust hood system maintenance report required/RN">>"One Garden State Plaza">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-00137">>"False">>"">>"">>"03/26/2025">>"1031.10">>"Emergency lighting equipment inspection and testing.">>"">>"Store">>"Emergency lighting power system shall be tested and report emailed to Fire Prevention/RN">>"One Garden State Plaza">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1743180294">>"False">>"">>"">>"03/28/2025">>"1008.2">>"Illumination required.">>"">>"South stairwell second floor landing">>"Emergency egress lighting shall be maintained">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742930485">>"False">>"">>"">>"03/25/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-00136">>"False">>"">>"">>"03/26/2025">>"901.6.3">>"Records.">>"">>"Store">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"One Garden State Plaza">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741716852">>"False">>"">>"">>"03/11/2025">>"1013">>"EXIT SIGNS">>"">>"3rd floor outside suite 312">>"Repair Exit Light (Battery Operation)">>"">>"">>"">>"">>"">
"FPVIO-25-1741714276">>"False">>"">>"">>"03/11/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743444712">>"False">>"Dogtas">>"Dogtas">>"03/31/2025">>"1031.3">>"Obstructions.">>"">>"rear exit">>"Means of egress shall not be obstructed">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1741717427">>"False">>"Ameriprise Financial dba Plaza 140 Services, LLC">>"Ameriprise Financial dba Plaza 140 Services, LLC">>"03/11/2025">>"1013">>"EXIT SIGNS">>"">>"Break Room">>"Repair Exit Light (Battery Operation)">>"">>"Paramus">>"">>"">>"">
"FPVIO-25-1743444528">>"False">>"Dogtas">>"Dogtas">>"03/31/2025">>"604.3">>"Working space and clearance.">>"">>"rear exit ">>"Storage not permitted within 36 inches of electrical service equipment">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1741718583">>"False">>"">>"">>"03/11/2025">>"610.1">>"General.">>"">>"By Receptionist ">>"Repair Emergency Light">>"">>"">>"">>"">>"">
"FPVIO-25-1741717480">>"False">>"Ameriprise Financial dba Plaza 140 Services, LLC">>"Ameriprise Financial dba Plaza 140 Services, LLC">>"03/11/2025">>"1013">>"EXIT SIGNS">>"">>"Hallway">>"Repair/replace exit light">>"">>"Paramus">>"">>"">>"">
"FPVIO-25-1743000537">>"False">>"">>"">>"03/26/2025">>"1008.2">>"Illumination required.">>"">>"front of sales floor">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1742999958">>"False">>"">>"">>"03/26/2025">>"315.3.1">>"Ceiling clearance.">>"">>"Backroom">>"Storage shall not be within 18 inches of ceiling in sprinklered building">>"">>"">>"">>"">>"">
"FPVIO-25-1743000022">>"False">>"">>"">>"03/26/2025">>"1008.2">>"Illumination required.">>"">>"By register">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1741713536">>"False">>"">>"">>"03/11/2025">>"907.8.1">>"Maintenance required.">>"">>"">>"Fire alarm maintenance required/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741714029">>"False">>"">>"">>"03/11/2025">>"1013.1">>"Exit signs.">>"">>"">>"Exit/direction signs shall be maintained/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742999890">>"False">>"">>"">>"03/26/2025">>"604.3">>"Working space and clearance.">>"">>"Backroom">>"Storage not permitted within 36 inches of electrical service equipment">>"">>"">>"">>"">>"">
"FPVIO-25-1741714259">>"False">>"">>"">>"03/11/2025">>"906.2">>"General requirements.">>"">>"">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742999915">>"False">>"">>"">>"03/26/2025">>"906.6">>"Unobstructed and unobscured.">>"">>"Backroom">>"Fire extinguisher access shall not be obstructed/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743444486">>"False">>"Dogtas">>"Dogtas">>"03/31/2025">>"315.3.3">>"Equipment rooms.">>"">>"fire alarm and sprinkler room">>"Storage not permitted in utility rooms">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743183519">>"False">>"">>"">>"03/28/2025">>"315.3.3">>"Equipment rooms.">>"">>"">>"Storage not permitted in utility rooms">>"">>"">>"">>"">>"">
"FPVIO-25-1743433981">>"False">>"">>"">>"03/31/2025">>"907.8.1">>"Maintenance required.">>"">>"">>"Fire alarm maintenance required/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741795724">>"False">>"">>"">>"03/12/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741795731">>"False">>"">>"">>"03/12/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"">>"">>"">
"FPVIO-25-00110">>"False">>"Chrysler Jeep Dodge">>"Chrysler Jeep Dodge">>"03/13/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"Attn. David Porter">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743001500">>"False">>"">>"">>"03/26/2025">>"703.1">>"Maintaining protection.">>"">>"Backroom">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741795740">>"False">>"">>"">>"03/12/2025">>"906.1">>"Where required.">>"">>"basement 3">>"Fire Extinguisher required">>"">>"">>"">>"">>"">
"FPVIO-25-1741795507">>"False">>"">>"">>"03/12/2025">>"315.3.1">>"Ceiling clearance.">>"">>"basement">>"Storage shall not be within 18 inches of ceiling in sprinklered building">>"">>"">>"">>"">>"">
"FPVIO-25-1743444384">>"False">>"Dogtas">>"Dogtas">>"03/31/2025">>"906.2">>"General requirements.">>"">>"side door">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743444425">>"False">>"Dogtas">>"Dogtas">>"03/31/2025">>"906.9">>"Extinguisher installation.">>"">>"front door">>"Fire extinguisher shall be properly mounted/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743444455">>"False">>"Dogtas">>"Dogtas">>"03/31/2025">>"906.2">>"General requirements.">>"">>"front door">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1741795345">>"False">>"">>"">>"03/12/2025">>"1031.3">>"Obstructions.">>"">>"">>"Means of egress shall not be obstructed">>"">>"">>"">>"">>"">
"FPVIO-25-1741795452">>"False">>"">>"">>"03/12/2025">>"703.1">>"Maintaining protection.">>"">>"">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743444204">>"False">>"Dogtas">>"Dogtas">>"03/31/2025">>"907.8.1">>"Maintenance required.">>"">>"showroom floor">>"Fire alarm maintenance required/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743444291">>"False">>"Dogtas">>"Dogtas">>"03/31/2025">>"901.4.1">>"Fire protection systems.">>"">>"">>"Fire Protection system maintenance required/CR. structure erected obstructs sprinkler coverage and access to remote test stations">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1741880574">>"False">>"Jewelry Center LLC">>"Jewelry Center LLC">>"03/13/2025">>"1013.1">>"Exit signs.">>"">>"Side entrance west side">>"Exit/direction signs shall be maintained/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742237983">>"False">>"">>"695 ROUTE 17">>"03/17/2025">>"315.3.3">>"Equipment rooms.">>"">>"Utility room">>"Storage not permitted in utility rooms">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742238085">>"False">>"">>"695 ROUTE 17">>"03/17/2025">>"604.3.1">>"Labeling.">>"">>"">>"Electrical room shall be clearly identified (Signage Required)/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743089355">>"False">>"">>"">>"03/27/2025">>"1008.2">>"Illumination required.">>"">>"1st floor hallway above exit from Say Cheez">>"Emergency egress lighting shall be maintained">>"">>"">>"">>"">>"">
"FPVIO-25-1742235631">>"False">>"Mercedes Benz of Paramus">>"Mercedes Benz of Paramus">>"03/17/2025">>"604.3">>"Working space and clearance.">>"">>"service bays west side ">>"Storage not permitted within 36 inches of electrical service equipment">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742238220">>"False">>"">>"695 ROUTE 17">>"03/17/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743088571">>"False">>"">>"">>"03/27/2025">>"604.3.1">>"Labeling.">>"">>"">>"Electrical Panel must have labeling for emergency lighting
">>"">>"">>"">>"">>"">
"FPVIO-25-1742238146">>"False">>"">>"695 ROUTE 17">>"03/17/2025">>"604.5">>"Extension cords.">>"">>"entrance door ">>"Extension cords shall not be utilized for permanent wiring">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743089147">>"False">>"">>"">>"03/27/2025">>"1013.1">>"Exit signs.">>"">>"1st Floor hallway above north exit ">>"Exit/direction signs shall be maintained/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743094201">>"False">>"">>"">>"03/27/2025">>"604.3.1">>"Labeling.">>"">>"Electrical Panel">>"Emergency Lighting breaker must be labeled on panel for testing/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743091452">>"False">>"">>"">>"03/27/2025">>"1008.2">>"Illumination required.">>"">>"Sales Floor">>"Emergency egress lighting shall be maintained

No emergency lighting when the breaker was hit for testing">>"">>"">>"">>"">>"">
"FPVIO-25-1742924109">>"False">>"">>"">>"03/25/2025">>"906.2">>"General requirements.">>"">>"Storage Room">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743094329">>"False">>"">>"">>"03/27/2025">>"906.2">>"General requirements.">>"">>"Behind Register">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743090130">>"False">>"">>"">>"03/27/2025">>"906.2">>"General requirements.">>"">>"Throughout ">>"Fire extinguisher overdue for maintenance/inspection/RN">>"2nd floor">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742235491">>"False">>"Mercedes Benz of Paramus">>"Mercedes Benz of Paramus">>"03/17/2025">>"1031.3">>"Obstructions.">>"">>"south west service office">>"Means of egress shall not be obstructed">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743091342">>"False">>"">>"">>"03/27/2025">>"906.2">>"General requirements.">>"">>"Backroom">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743090150">>"False">>"">>"">>"03/27/2025">>"704.2">>"Opening protectives.">>"">>"">>"Fire doors shall not be blocked open or obstructed">>"2nd floor">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1743088312">>"False">>"">>"">>"03/27/2025">>"604.3">>"Working space and clearance.">>"">>"Electrical Panel">>"Storage not permitted within 36 inches of electrical service equipment">>"">>"">>"">>"">>"">
"FPVIO-25-1742239185">>"False">>"">>"695 ROUTE 17">>"03/17/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742239190">>"False">>"">>"695 ROUTE 17">>"03/17/2025">>"906.6">>"Unobstructed and unobscured.">>"">>"front door
">>"Fire extinguisher access shall not be obstructed/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742239029">>"False">>"">>"695 ROUTE 17">>"03/17/2025">>"1031.3">>"Obstructions.">>"">>"rear exit
">>"Means of egress shall not be obstructed">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742239133">>"False">>"">>"695 ROUTE 17">>"03/17/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742306884">>"False">>"">>"">>"03/18/2025">>"906.2">>"General requirements.">>"">>"Front Vestibule">>"Fire extinguishers must be properly charged, serviced and tagged">>"">>"">>"">>"">>"">
"FPVIO-25-1742306979">>"False">>"">>"">>"03/18/2025">>"102.1.1">>"">>"">>"">>"Remove obstructions away from the exit door">>"">>"">>"">>"">>"">
"FPVIO-25-1742239235">>"False">>"">>"695 ROUTE 17">>"03/17/2025">>"703.1">>"Maintaining protection.">>"">>"near front door">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743086871">>"False">>"">>"">>"03/27/2025">>"906.2">>"General requirements.">>"">>"Throughout">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742238608">>"False">>"">>"695 ROUTE 17">>"03/17/2025">>"906.2">>"General requirements.">>"">>"Throughout">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742238644">>"False">>"">>"695 ROUTE 17">>"03/17/2025">>"315.3.3">>"Equipment rooms.">>"">>"Electrical Room">>"Storage not permitted in utility rooms">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743087943">>"False">>"">>"">>"03/27/2025">>"1031.3">>"Obstructions.">>"">>"">>"Means of egress shall not be obstructed">>"">>"">>"">>"">>"">
"FPVIO-25-1742238227">>"False">>"">>"695 ROUTE 17">>"03/17/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743087525">>"False">>"">>"">>"03/27/2025">>"906.2">>"General requirements.">>"">>"">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742238981">>"False">>"">>"695 ROUTE 17">>"03/17/2025">>"1013.1">>"Exit signs.">>"">>"rear exit">>"Exit/direction signs shall be maintained/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743087582">>"False">>"">>"">>"03/27/2025">>"604.3">>"Working space and clearance.">>"">>"Electrical Panel ">>"Storage not permitted within 36 inches of electrical service equipment">>"">>"">>"">>"">>"">
"FPVIO-25-1742238716">>"False">>"">>"695 ROUTE 17">>"03/17/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1741975054">>"False">>"">>"">>"03/14/2025">>"1008.2">>"Illumination required.">>"">>"2nd floor chapel ">>"Emergency egress lighting shall be maintained. (battery)">>"">>"">>"">>"">>"">
"FPVIO-25-1742926311">>"False">>"">>"">>"03/25/2025">>"1013.1">>"Exit signs.">>"">>"break room">>"Exit/direction signs shall be maintained/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741974998">>"False">>"">>"">>"03/14/2025">>"906.2">>"General requirements.">>"">>"">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1742926790">>"False">>"">>"">>"03/25/2025">>"315.3.3">>"Equipment rooms.">>"">>"electrical room">>"Storage not permitted in utility rooms">>"">>"">>"">>"">>"">
"FPVIO-25-1741975695">>"False">>"">>"">>"03/14/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Sprinkler inspection report shall be emailed to Fire Prevention Bureau/RN/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741975669">>"False">>"">>"">>"03/14/2025">>"901.6.3">>"Records.">>"">>"">>"Annual Fire Alarm inspection report shall be emailed to Fire Prevention Bureau/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741974373">>"False">>"">>"">>"03/14/2025">>"1013.1">>"Exit signs.">>"">>"Sales floor front half of the store">>"Exit/direction signs shall be maintained/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741888145">>"False">>"Chrysler Jeep Dodge">>"Chrysler Jeep Dodge">>"03/13/2025">>"503.4">>"Obstruction of fire apparatus access roads.">>"">>"4 vehicles ">>"Fire lane shall not be obstructed">>"Attn. David Porter">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1741887897">>"False">>"Chrysler Jeep Dodge">>"Chrysler Jeep Dodge">>"03/13/2025">>"5303.5.3">>"Securing compressed gas containers, cylinders and tanks.">>"">>"north service area">>"Compressed gas cylinders/containers shall be secured">>"Attn. David Porter">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743176483">>"False">>"">>"">>"03/28/2025">>"703.1">>"Maintaining protection.">>"">>"common area behind Phoenix/Mantra">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741974059">>"False">>"">>"">>"03/14/2025">>"703.1">>"Maintaining protection.">>"">>"Bathroom and storage room">>"Holes in fire rated walls/ceilings shall be repaired/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741887736">>"False">>"Chrysler Jeep Dodge">>"Chrysler Jeep Dodge">>"03/13/2025">>"906.2">>"General requirements.">>"">>"wash bay">>"Fire extinguisher overdue for maintenance/inspection/RN">>"Attn. David Porter">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742926273">>"False">>"">>"">>"03/25/2025">>"1013.1">>"Exit signs.">>"">>"rear near shampoo">>"Exit/direction signs shall be maintained/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1742926863">>"False">>"">>"">>"03/25/2025">>"906.2">>"General requirements.">>"">>"electrical room">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1743095351">>"False">>"">>"">>"03/27/2025">>"906.2">>"General requirements.">>"">>"Front of store">>"Fire extinguisher overdue for maintenance/inspection/RN">>"1206">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1743095341">>"False">>"">>"">>"03/27/2025">>"604.6">>"Unapproved conditions.">>"">>"Backroom ">>"Open Electrical Junction boxes / wiring is prohibited/RN">>"1206">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1743094468">>"False">>"">>"">>"03/27/2025">>"906.6">>"Unobstructed and unobscured.">>"">>"Backroom next to electrical panel">>"Fire extinguisher access shall not be obstructed/RN">>"">>"">>"">>"">>"">
"FPVIO-25-1741880637">>"False">>"Jewelry Center LLC">>"Jewelry Center LLC">>"03/13/2025">>"1008.2">>"Illumination required.">>"">>"happy diamonds
jewelry by Alex
La Belle
haniken
sweet treasures
Nicole's jewelry
Special orders
design by LA
Jack Gabriel
Harry's jewelry
Bektas">>"Emergency egress lighting shall be maintained">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1742235155">>"False">>"Mercedes Benz of Paramus">>"Mercedes Benz of Paramus">>"03/17/2025">>"1031.1.1">>"Storage.">>"">>"North Stairwell">>"Storage not permitted in means of egress/RN">>"">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743099864">>"False">>"">>"">>"03/27/2025">>"906.2">>"General requirements.">>"">>"Throughout">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1743100004">>"False">>"">>"">>"03/27/2025">>"1031.10">>"Emergency lighting equipment inspection and testing.">>"">>"">>"Emergency lighting power system shall be tested and report emailed to Fire Prevention/RN">>"">>"">>"New Jersey">>"07652">>"">
"FPVIO-25-1741886945">>"False">>"Chrysler Jeep Dodge">>"Chrysler Jeep Dodge">>"03/13/2025">>"1031.1.1">>"Storage.">>"">>"">>"Storage not permitted in means of egress/RN">>"Attn. David Porter">>"Paramus">>"New Jersey">>"07652">>"">
"FPVIO-25-1743176550">>"False">>"">>"">>"03/28/2025">>"1008.2">>"Illumination required.">>"">>"common area behind Phoenix/Mantra">>"Exit sign needs egress lighting ">>"">>"">>"">>"">>"">
"FPVIO-25-1743098986">>"False">>"">>"">>"03/27/2025">>"906.2">>"General requirements.">>"">>"">>"Fire extinguisher overdue for maintenance/inspection/RN">>"">>"">>"New Jersey">>"07652">>"">